Basic Boiler Calculations
Feedwater = Make up + Condensate Return
Feedwater Flow (FWF) = Steam Make + Blowdown(BD)
Feedwater Flow (FWF) = Steam Make + Steam Make Cycles -1
Blowdown = Steam make Cycle-1Â or = FWF CyclesÂ
% Blowdown = as a % of FWF Cycles
Condensate Return is also expressed as % of FWF
If Condensate Return = 60% Make up = 40%
% Condensate + % Make up = 100% = FWF
As the boiler water cycles of concentration increase then the feedwater flow and the steam make approach the same number
Calculate the feedwater composition (impurities) from make up and condensate analysis below